Compact, Reliable Chlorine Gas Filtration for Industrial and Municipal Systems
The C‑100 Chlorine Gas Filter is a high-performance filtration unit designed to remove moisture and particulates from chlorine gas lines. Featuring a dual-chamber design, this rugged filter serves both as a liquid trap and a fine particulate filter, helping to safeguard regulators, chlorinators, and downstream components in your gas feed system.
Whether used in a municipal water treatment facility or a high-volume industrial setting, the C‑100 Gas Filter enhances the reliability, safety, and longevity of your chlorination process.
How the C‑100 Gas Filter Works
The C‑100 Chlorine Gas Line Filter is built with a two-stage internal design:
- Lower Chamber – Liquid Trap
Incoming chlorine gas slows as it enters the filter, allowing entrained liquid chlorine and ferric chloride residue to settle at the bottom of the chamber. This process prevents moisture from reaching sensitive downstream equipment. - Upper Chamber – Filter Cartridge
Gas then passes through a removable fiberglass cartridge and pad system designed to capture fine particulate matter. The result is a clean, dry chlorine gas supply that supports optimal system function and protects metering valves, feed regulators, and gas feed equipment.
Installation Guidance
To ensure proper operation and maximize protection, install the C‑100 Chlorine Gas Filter as follows:
- Immediately after chlorine ton cylinders, bulk evaporators, or supply manifolds
- Before any pressure-reducing valves or flow control devices
- In a vertical orientation, with enough clearance beneath the filter for pad replacement
- Use inline unions or pressurized gas manifolds for easier servicing
The C‑100 Gas Filter is compatible with a variety of chlorination setups, including liquid feed systems and conventional vacuum systems.