The Hydro Instruments chlorine calculator sizes a chlorine gas supply from two numbers: your feed rate and the coldest temperature your chlorine room reaches. It shows how many 150 lbs. cylinders or ton containers to connect, how long they last, and when you need a vaporizer. One ton container gives about 8 lb/day of gas for each °F of room temperature, about 480 lb/day (9 kg/hr) at 60°F (16°C). Above about 2,000 PPD (40 kg/hr), a vaporizer is typically considered.
Chlorine containers and vaporizers
Size your chlorine supply from two numbers
Rather talk it through? Call Hydro at 215-799-0980.
Results
Ton containers · gas withdrawal
3online+3standby
At 1,200 PPD (22.7 kg/hr) and 55°F (12.8°C), connect 3 ton containers on gas withdrawal and keep a matching set of 3 on standby.
- Online set lasts
- 5 days
- Used a month
- 18.2
- Gas from one ton container
- 440 lb/day
- Vaporizer
- Not needed
The quote button copies these numbers. Paste them into the message box on the form.
The same chlorine as 15% sodium hypochlorite
960gallons a day
6.5truckloads a month
Chlorine, ton containers
15% sodium hypochlorite, truckloads
15% sodium hypochlorite carries about 1.25 lb of chlorine per gallon. No strength loss in storage is counted, so the truck count is the minimum. Bleach vs. gas chlorination
What these results assume
- One ton container gives about 8 lb/day of gas for each °F of room temperature: 400 lb/day at 50°F, 480 lb/day at 60°F and 544 lb/day at 68°F.
- One 150 lbs. cylinder gives about 1 lb/day of gas for each °F: 50 lb/day at 50°F and 68 lb/day at 68°F.
- Both rates are dependable long-term figures from the Hydro Chlorine Handling Manual, with at least 35 psig back pressure. The room stays between 50 and 122°F (10 and 50°C).
- Liquid withdrawal with a vaporizer is typically considered above 2,000 PPD (40 kg/hr). Chlorine cargo tanks and rail cars are always liquid withdrawal.
- Results show the containers online, rounded up, plus a matching standby set for changeover.
- A container lasts until all of its chlorine is used. A month is 30.4 days.
- Vaporizer limits are checked in the unit you enter, against Hydro ratings that pair 2,000 PPD with 40 kg/hr. Other conversions use 1 kg/hr = 52.9 lb/day.
- These are planning figures. Hydro Instruments confirms the equipment for your site.
Chlorine withdrawal rate per ton container and cylinder, by room temperature
The gas withdrawal rate from a chlorine container depends on room temperature. Liquid chlorine evaporates inside the container before it leaves as gas, and the heat for that comes from the room air. One ton container gives a dependable 8 lb/day for each °F of room temperature, and one 150 lbs. cylinder about 1 lb/day per °F. At 60°F (16°C), that is about 480 lb/day (9 kg/hr) from a ton container. Source: Hydro Instruments, Chlorine Handling Manual, section 4, Withdrawal Rates.
| Room temperature | One ton container | One 150 lbs. cylinder |
|---|---|---|
| 50°F (10°C) | 400 lb/day (7.6 kg/hr) | 50 lb/day |
| 60°F (16°C) | 480 lb/day (9.1 kg/hr) | 60 lb/day |
| 68°F (20°C) | 544 lb/day (10.3 kg/hr) | 68 lb/day |
| 86°F (30°C) | 688 lb/day (13 kg/hr) | 86 lb/day |
| 104°F (40°C) | 832 lb/day (15.7 kg/hr) | 104 lb/day |
| 122°F (50°C) | 976 lb/day (18.4 kg/hr) | 122 lb/day |
Dependable long-term rates with at least 35 psig back pressure, from the Hydro Chlorine Handling Manual. Metric figures use 1 kg/hr = 52.9 lb/day.
Pull gas faster than the room can supply heat and the container cools. Pressure falls with it, frost forms on the outside, and the vacuum regulator closes as if the container were empty.
Chlorine room temperature: 50 to 122°F, and how to get more gas
Hydro's rule is to keep the chlorine room between 50 and 122°F (10 and 50°C), and the calculator stops outside that range. The Hydro Chlorine Handling Manual recommends 60 to 120°F (15 to 50°C) for chlorine storage, for safe and steady discharge rates. The VPH-10000 vaporizer is rated for room temperatures of 50 to 122°F (10 to 50°C), so the same range applies on liquid withdrawal.
Three things get more gas from the containers you already have:
- Move the air. A fan that blows room air across the containers is the most effective way to raise the rate from a single container.
- Heat the room, never the containers. The fusible plugs melt between 158 and 165°F (70 to 74°C) and release the chlorine. If the room has heaters, fit a high air temperature sensor wired to shut them off.
- Keep the containers matched. Every container on a manifold sits at the same temperature and elevation, so they feed evenly.
How many chlorine cylinders or ton containers to connect
The number of chlorine containers to keep online is the feed rate divided by the withdrawal rate at your coldest room temperature, rounded up. Add a matching standby set, so an automatic changeover system keeps chlorine feeding when the online set runs empty.
Worked exampleA plant feeds 1,200 PPD and its chlorine room drops to 55°F in winter. One ton container gives 440 lb/day at 55°F (8 × 55). 1,200 ÷ 440 = 2.73, rounded up to 3 ton containers online, with 3 on standby. The online set holds 6,000 lb and lasts 5 days.
One Hydro pressure manifold connects up to five containers. Models HM-121 to HM-125 take 150 lbs. cylinders, and HMT-121 to HMT-125 take ton containers on gas withdrawal. More than five online means a second manifold or the next container size up.
Hydro's first choice is simpler still. Where possible, mount a vacuum regulator directly on each container and join them with a vacuum manifold. Then no chlorine is piped under pressure.
How long a chlorine cylinder or ton container lasts at your feed rate
A chlorine container lasts its chlorine weight divided by the feed rate in lb/day. The table shows one container at common feed rates. With several online, multiply by the number of containers in the set.
| Feed rate | 150 lbs. cylinder | Ton container | Chlorine cargo tank | Rail car |
|---|---|---|---|---|
| 100 PPD (2 kg/hr) | 1.5 days | 20 days | 280 days | 1,800 days |
| 500 PPD (10 kg/hr) | 7.2 hours | 4 days | 56 days | 360 days |
| 2,000 PPD (40 kg/hr) | – | 1 day | 14 days | 90 days |
| 5,000 PPD (100 kg/hr) | – | 9.6 hours | 5.6 days | 36 days |
| 10,000 PPD (200 kg/hr) | – | 4.8 hours | 2.8 days | 18 days |
| 15,000 PPD (300 kg/hr) | – | 3.2 hours | 1.9 days | 12 days |
Chlorine held: 150 lb, 2,000 lb, 28,000 lb and 180,000 lb. A chlorine cargo tank is counted at 14 tons, the low end of its usual fill. Each container is counted until all of its chlorine is used. A dash means the feed rate is far beyond what cylinders can supply.
When you need a chlorine vaporizer or evaporator
Liquid chlorine withdrawal with a vaporizer is typically considered above 2,000 PPD (40 kg/hr). The line is not sharp. At 68°F, 2,000 PPD already takes four ton containers online on gas withdrawal, and the count keeps climbing with the feed rate, so at some point a vaporizer is more practical than more containers. Hydro suggests staying on gas withdrawal wherever possible, because a liquid system adds complexity and safety concerns.
A vaporizer, also called a chlorine evaporator, is fed liquid chlorine from the bottom valve of a ton container, or from a chlorine cargo tank or rail car. One ton container can deliver up to 9,600 PPD (180 kg/hr) as liquid, and a chlorine cargo tank up to 8,000 lb/hr (3,636 kg/hr). Chlorine cargo tanks and rail cars are unloaded as liquid only, so they always feed through a vaporizer.
- Up to 10,000 PPD (200 kg/hr): the VPH-10000, with an 18 kW heater.
- Up to 15,000 PPD (300 kg/hr): the VPH-10000-1A, with a 30 kW heater and recirculating pump.
- Above 15,000 PPD: more than one vaporizer.
Each vaporizer is installed with at least one expansion chamber assembly, one pressure relief assembly and one electrically actuated pressure reducing valve.
Feeding more than 2,000 PPD?See the VPH-10000 vaporizers, expansion chambers and pressure reducing valves.
Chlorine gas cylinder sizes, from 150 lb cylinders to rail cars
Which chlorine container fits depends on the feed rate, rail access, and how much chlorine your state and local rules allow on site. Most rules limit on-site storage, so check them before choosing.
| Container | Chlorine held | Size and weight | Withdrawal |
|---|---|---|---|
| 150 lbs. cylinder | 150 lb | 10.25 to 10.75 in diameter, 4 ft 5 in to 4 ft 8 in tall, 235 to 290 lb full | Gas only |
| Ton container (tonner) | 2,000 lb | 30 in diameter, 80 in long, 3,300 to 3,650 lb full | Gas or liquid |
| Chlorine cargo tank | 17 ton capacity, filled with 14 to 16 tons (28,000 to 32,000 lb). The calculator uses 14 tons | Semi-trailer, delivered by road. Truck weight limits keep the fill below capacity | Liquid only |
| Rail car | 90 tons (180,000 lb) | Delivered by rail. Cars range from 16 to 90 tons | Liquid only |
Cylinder and ton container figures from the Hydro Chlorine Handling Manual and the ton container manifold guide.
- 150 lbs. cylinder. Best for small systems, up to about 340 lb/day at 68°F with five online. Falls short as the feed rate rises: more than five online needs a second manifold.
- Ton container. Best for about 300 to 2,000 PPD on gas withdrawal. Falls short at higher feed rates, where each container empties within a day.
- Chlorine cargo tank. Best for feed rates that empty a ton container in hours, at plants without rail access. Always needs a vaporizer.
- Rail car. Best for the largest feed rates at plants with rail access. Always needs a vaporizer.
Chlorine gas vs 15% sodium hypochlorite: one rail car equals 32 truckloads
A gallon of 15% sodium hypochlorite carries about 1.25 lb of chlorine, so the same feed rate takes far more deliveries as hypochlorite than as chlorine gas. One rail car of chlorine equals about 32 hypochlorite truckloads of 4,500 gallons.
| Feed rate | 15% sodium hypochlorite | Truckloads of 4,500 gal | Chlorine containers |
|---|---|---|---|
| 500 PPD | 400 gal/day | 2.7 a month | 7.6 ton containers a month |
| 2,000 PPD | 1,600 gal/day | 10.8 a month | 30 ton containers a month |
| 5,000 PPD | 4,000 gal/day | 27 a month | 5.4 chlorine cargo tanks a month |
| 10,000 PPD | 8,000 gal/day | 54 a month, 1.8 a day | 1.7 rail cars a month |
A month is 30.4 days. The truck count is a minimum: sodium hypochlorite loses strength in storage, and no loss is counted here.
The 1.25 lb figure scales from Hydro's own comparison of chlorine gas and 12.5% sodium hypochlorite, which works out to about 1.04 lb of chlorine per gallon. Hydro compares the two chemicals in Bleach vs. Gas Chlorination.
How the chlorine calculator works: formulas and assumptions
The Hydro chlorine calculator on this page sizes a chlorine supply from the feed rate and the coldest room temperature. It uses the withdrawal rates in the first table and these formulas.
- Feed rate from flow and dose. MGD × mg/L × 8.34 = PPD, or m³/h × mg/L ÷ 1,000 = kg/hr. Hydro's Formulas and Conversions page gives the GPM version: GPM × 0.012 × PPM = PPD.
- Withdrawal rate. 8 lb/day × room °F for one ton container, and 1 lb/day × room °F for one 150 lbs. cylinder.
- Containers online. Feed rate ÷ withdrawal rate at the coldest room temperature, rounded up, plus a matching standby set.
- Vaporizer. From 2,000 PPD (40 kg/hr), and always for chlorine cargo tanks and rail cars.
- Container life. Chlorine held ÷ feed rate. Containers a month = feed rate × 30.4 ÷ chlorine held.
- 15% sodium hypochlorite. Gallons a day = feed rate ÷ 1.25. Truckloads a month = gallons a day × 30.4 ÷ truck size.
- Units. Vaporizer limits are checked in the unit you enter, against Hydro ratings that pair 2,000 PPD with 40 kg/hr. Everything else uses the exact conversion, 1 kg/hr = 52.9 lb/day.
The results are planning figures. Hydro Instruments confirms the equipment for your site. Chlorine is hazardous, so follow your safety procedures and local codes.
Common questions about chlorine cylinders, ton containers and vaporizers
How many pounds of chlorine can you withdraw from a ton container per day?
One ton container gives about 8 lb/day of chlorine gas for each °F of room temperature: about 480 lb/day (9 kg/hr) at 60°F (16°C) and 544 lb/day at 68°F (20°C). At 50°F (10°C), it gives about 400 lb/day. A higher feed rate needs more ton containers online, or liquid withdrawal with a vaporizer.
How much chlorine can a 150 lb cylinder supply per day?
A 150 lbs. chlorine cylinder supplies about 1 lb/day of gas for each °F of room temperature, about 68 lb/day at 68°F (20°C). The Hydro Instruments Chlorine Handling Manual gives this as the dependable rate, so a colder room gives less: about 50 lb/day at 50°F (10°C). A higher feed rate needs more cylinders connected, or ton containers.
How long does a ton container of chlorine last?
A ton container of chlorine lasts 2,000 lb divided by the feed rate in lb/day. A ton container lasts 20 days at 100 PPD, 4 days at 500 PPD and 1 day at 2,000 PPD. With several ton containers online, the set lasts that many times longer.
At what feed rate do you need a chlorine vaporizer?
A chlorine vaporizer is typically considered when the feed rate goes above 40 kg/hr (2,000 PPD). Below that, gas withdrawal from 150 lbs. cylinders or ton containers is simpler, and Hydro Instruments suggests it wherever possible. Chlorine cargo tanks and rail cars are liquid withdrawal only, so they always need a vaporizer.
How many ton containers can you connect to one manifold?
One Hydro Instruments manifold connects one to five ton containers: models HMT-121 to HMT-125 for gas withdrawal and HML-121 to HML-125 for liquid withdrawal. A feed rate that needs more than five ton containers online needs a second manifold, or liquid withdrawal with a vaporizer.
How much 15% sodium hypochlorite equals a ton container of chlorine?
One ton container of chlorine equals about 1,600 gallons of 15% sodium hypochlorite. The ton container holds 2,000 lb of chlorine, and a gallon of 15% sodium hypochlorite carries about 1.25 lb. A rail car of chlorine, at 180,000 lb, equals about 144,000 gallons, or 32 truckloads of 4,500 gallons.
Send Hydro your feed rate and room temperature.We size the manifolds, changeover system and vaporizer for your site.
Figures from Hydro Instruments documents: Chlorine Handling Manual (CL2-001, rev. July 22, 2025), Gas Feed Rate Limits for Long Term Feed, Ton Container Manifolds for Gas Withdrawal Systems (TCMGWS-DC, rev. June 9, 2026), Pressure Manifolds bulletin (rev. April 13, 2023), VPH-10000 bulletin (rev. October 5, 2026) and VPH-10000-1A bulletin (rev. February 18, 2017). Technical review: Alan Morgan, President, Hydro Instruments.